Model
E-704 and SE-704 Technical Data |
| Net Output Maximum Load |
6866 |
kW |
| Modulation Range |
20-100 |
% |
| Equivalent Maximum Output Saturated
Steam (*) |
10958 |
kg/h |
| Nominal Operating Steam Pressures
Upto: (**) |
58 |
barg |
| Standard installed
Electrical Motor Power (230/400/415/440 VAC
- 50/60 Hz) |
Water Pump |
2 x 11 |
kW |
| Blower |
45 |
kW |
| Combustion Efficiency (***)
Without Economiser (E Model) |
Full load |
Gas |
91 |
% |
| Light Oil |
90 |
% |
| Min load |
Gas |
92 |
% |
| Light Oil |
91 |
% |
| Combustion Efficiency
(***)
With Economiser (SE Model)
|
Full load |
Gas |
93 |
% |
| Light Oil |
92 |
% |
| Min load |
Gas |
94 |
% |
| Light Oil |
93 |
% |
| Fuel Consumption at Full
Load Without Economiser (E Model) |
Gas - LCV 37000 kJ/Nm3 |
737 |
Nm3/h |
| Light Oil - LCV 42700 kJ/kg |
657 |
kg/h |
| Fuel Consumption at Full
Load With Economiser (SE Model) |
Gas - LCV 37000 kJ/Nm3 |
720 |
Nm3/h |
| Light Oil - LCV 42700 kJ/kg |
643 |
kg/h |
| Atomising Air (Oil Fired
Units Only) |
Required Flow |
40 |
Nm3/h |
| Required Pressure |
5-7 |
barg |
| Water Content
(generator water/steam system)
Without Economiser (E Model) |
Filled |
2109 |
litres |
| In Operation |
1150 |
litres |
| Water Content
(generator water/steam system)
With Economiser (SE Model) |
Filled |
2375 |
litres |
| In Operation |
1350 |
litres |
| Overall Generator
Dimensions (approx) |
Length |
Gas |
3320 |
mm |
| Oil |
3100 |
mm |
| Gas Oil |
3320 |
mm |
| Width |
All Fuels |
3200 |
mm |
| Height Without Economiser |
All Fuels |
5200 |
mm |
| Height With Economiser |
All Fuels |
5845 |
mm |
| Weight Empty Without Economiser |
All Fuels |
8,600 |
kg |
| Weight Empty With Economiser |
All Fuels |
9400 |
kg |
| Overall Pump Skid
Dimensions (approx) |
Number of Skids per Generator |
2 |
|
| Length |
1350 |
mm |
| Width |
820 |
mm |
| Height |
1155 |
mm |
| Weight |
400 |
kg |
| Generator Stack Connection (Outer
Diameter) |
806 |
mm |
|
NOTES
(*) @ 1 bar a (absolute)
with feed water temperature of 100 °C
(**) Available as standard. Higher pressure(s) available on request.
(***) based on feed water
temperature of 60 °C |