Model
E-404 and SE-404 Technical Data |
| Net Output Maximum Load |
3924 |
kW |
| Modulation Range |
20-100 |
% |
| Equivalent Maximum Output Saturated
Steam (*) |
6263 |
kg/h |
| Nominal Operating Steam Pressures
Upto: (**) |
58 |
barg |
| Standard installed
Electrical Motor Power (230/400/415/440 VAC
- 50/60 Hz) |
Water Pump |
2 x 5.5 |
kW |
| Blower |
22 |
kW |
| Combustion Efficiency (***)
Without Economiser (E Model) |
Full load |
Gas |
91 |
% |
| Light Oil |
92 |
% |
| Min load |
Gas |
96 |
% |
| Light Oil |
97 |
% |
| Combustion Efficiency
(***)
With Economiser (SE Model)
|
Full load |
Gas |
95 |
% |
| Light Oil |
95 |
% |
| Min load |
Gas |
97 |
% |
| Light Oil |
97 |
% |
| Fuel Consumption at Full
Load Without Economiser (E Model) |
Gas - LCV 37000 kJ/Nm3 |
420 |
Nm3/h |
| Light Oil - LCV 42700 kJ/kg |
360 |
kg/h |
| Fuel Consumption at Full
Load With Economiser (SE Model) |
Gas - LCV 37000 kJ/Nm3 |
402 |
Nm3/h |
| Light Oil - LCV 42700 kJ/kg |
348 |
kg/h |
| Atomising Air (Oil Fired
Units Only) |
Required Flow |
40 |
Nm3/h |
| Required Pressure |
5-7 |
barg |
| Water Content
(generator water/steam system)
Without Economiser (E Model) |
Filled |
1495 |
litres |
| In Operation |
665 |
litres |
| Water Content
(generator water/steam system)
With Economiser (SE Model) |
Filled |
1721 |
litres |
| In Operation |
930 |
litres |
| Overall Generator
Dimensions (approx) |
Length |
Gas |
3060 |
mm |
| Oil |
2840 |
mm |
| Gas Oil |
3190 |
mm |
| Width |
All Fuels |
2130 |
mm |
| Height Without Economiser |
All Fuels |
3410 |
mm |
| Height With Economiser |
All Fuels |
3975 |
mm |
| Weight Empty Without Economiser |
All Fuels |
5800 |
kg |
| Weight Empty With Economiser |
All Fuels |
6600 |
kg |
| Overall Pump Skid
Dimensions (approx) |
Number of Skids per Generator |
2 |
|
| Length |
1350 |
mm |
| Width |
820 |
mm |
| Height |
1155 |
mm |
| Weight |
400 |
kg |
| Generator Stack Connection (Outer
Diameter) |
806 |
mm |
|
NOTES
(*) @ 1 bar a (absolute)
with feed water temperature of 100 °C
(**) Available as standard. Higher pressure(s) available on request.
(***) based on feed water
temperature of 60 °C |