Steam Generators and Exhaust Gas Boilers 150 - 40,000 kg/h
 

Model E-254 and SE-254 Technical Data

Net Output Maximum Load 2452 kW
Modulation Range 20-100 %
Equivalent Maximum Output Saturated Steam (*) 3914 kg/h
Nominal Operating Steam Pressures Upto: (**) 58 barg
Standard installed Electrical Motor Power

(230/400/415/440 VAC - 50/60 Hz)

Water Pump 7.5 kW
Blower 11 kW
Combustion Efficiency  (***)

Without Economiser (E Model)

Full load Gas 92 %
Light Oil 93 %
Min load Gas 95 %
Light Oil 95 %
Combustion Efficiency  (***)

With Economiser (SE Model)

 

Full load Gas 94 %
Light Oil 95 %
Min load Gas 96 %
Light Oil 97 %
Fuel Consumption at Full Load

Without Economiser (E Model)

Gas - LCV 37000 kJ/Nm3 259 Nm3/h
Light Oil - LCV 42700 kJ/kg 222 kg/h
Fuel Consumption at Full Load

With Economiser (SE Model)

Gas - LCV 37000 kJ/Nm3 254 Nm3/h
Light Oil - LCV 42700 kJ/kg 218 kg/h
Atomising Air (Oil Fired Units Only) Required Flow 27 Nm3/h
Required Pressure 5-7 barg
Water Content (generator water/steam system)

Without Economiser (E Model)

Filled 556 litres
In Operation 288 litres
Water Content (generator water/steam system)

With Economiser (SE Model)

Filled 695 litres
In Operation 431 litres
Overall Generator Dimensions (approx) Length Gas 2745 mm
Oil 2550 mm
Gas Oil 2872 mm
Width All Fuels 1950 mm
Height Without Economiser All Fuels 2785 mm
Height With Economiser All Fuels 3165 mm
Weight Empty Without Economiser All Fuels 3150 kg
Weight Empty With Economiser All Fuels 3650 kg
Overall Pump Skid Dimensions (approx) Number of Skids per Generator 1  
Length 1350 mm
Width 820 mm
Height 1155 mm
Weight 400 kg
Generator Stack Connection (Outer Diameter) 713 mm

NOTES

(*) @ 1 bar a (absolute) with feed water temperature of 100 °C       (**) Available as standard. Higher pressure(s) available on request.

(***) based on feed water temperature of 60 °C

 