Steam Generators and Exhaust Gas Boilers 150 - 40,000 kg/h
 

Blowdown Tanks

Ancilliaries

Home Page

Steam Generators

Exhaust Gas Boilers

Service Department

Spares Department

Steam Basics

Literature

Play Video

Copyright © 2007

 

 
  IN COMPLIANCE WITH PM60 FROM THE UK HEALTH & SAFETY EXECUTIVE

The Clayton Blowdown Tank is designed to safely handle the discharges from the automatic or manual blowdown on the Clayton Steam Generator. Water is collected in the sump of the vessel so that it cools naturally. Any additional water entering the tank replaces this standing water, which overflows into the outlet.

If required, a thermostatically controlled forced cooling system can be provided which will reduce the water temperature to around 40OC. This system is particularly useful when several boilers are connected to the same tank.

Designed to PD5500:2000 Cat 3 (Lloyds inspected) PED compliant. Design pressure 7 barg. Design Temperature 171 Deg C. Material BS1501-151 Grade 430A

 

135286UK

135287UK

135288UK

135294UK

135301UK

Standing Water (L)

25

40

90

200

350

Vessel Volume (L)

50

80

180

400

700

 Dimensions

A (mm)

305

305

457

610

762

B (mm)

1100

1500

1595

1845

2085

C (mm)

625

825

900

1025

1150

D (mm)

750

1050

1100

1275

1450

E (mm)

120

120

175

235

290

F (Dia) (mm)

15

15

15

15

15

G (mm)

220*

220*

308*

385*

475*

*approximate

 Connections

H (Inlet)

1” BSP

1” BSP

1 ¼” BSP

1 ½” BSP

2” BSP

I (Vent)

100NB

PN16

100NB

PN16

125NB

PN16

150NB

PN16

200NB

PN16

J (Cleanout)

2” BSP

2” BSP

2” BSP

2” BSP

2” BSP

K (Outlet)

1½” BSP

1½” BSP

2” BSP

2” BSP

80NB PN16

L (Cooling Water )

¾” BSP

¾” BSP

¾” BSP

¾” BSP

¾” BSP

M (Temp Sensor)

1” BSP

1” BSP

1” BSP

1” BSP

1” BSP

N (Press Gauge)

3/8” BSP

3/8” BSP

3/8” BSP

3/8” BSP

3/8” BSP

Inspection Opening

2” BSP

2” BSP

150NB

PN16

150NB

PN16

200NB

PN16